EasyManua.ls Logo

Iskra FPC 200 - Technical Characteristics

Default Icon
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
170 USER MANUAL FPC 200 - 3/2017
6.2 Technical characteristics
Device power supply
Rated voltage
DC or
24 V - 48 V
AC/DC
100 V - 250 V, 50 Hz, 60 Hz
Permissible tolerance
-20 % to +10 %
Power consumption
7 VA, typical 3 VA (without external
modules)
Voltage loss hold up time
100 ms (100 % drop)
Permanent memory type
EEPROM, FLASH
Permanent registers storing time
permanently
Galvanic isolation
AC
3,5 kV; 50 Hz; 1 min
AC current inputs
Nominal current
1 A / 5 A (defined by software setting)
Nominal frequency
50 Hz / 60 Hz
Measuring range
phase inputs
up to 55
sensitive (earth) input

Overvoltage category
CAT III 300 V
Consumption
≤ 0,1 VA (
), ≤ 0,1 VA (20
)
Thermal overload
Continuous
4
(20 A)
10 s
15
(75 A)
1 s
100
(500 A)
Galvanic isolation
AC
3,5 kV; 50 Hz; 1 min
AC voltage inputs
Nominal voltage
60 V - 500 V (defined by software setting)
Nominal frequency
50 Hz / 60 Hz
Measuring range
up to 500 V
Overvoltage category
CAT III 600 V
Input impedance
660 kΩ
Consumption
up to 250 V
0,1 VA
250 V - 500 V
0,4 VA
Maximum input voltage
Continuous
600 V; 50 Hz - 60 Hz
Galvanic isolation
AC
4,35 kV; 50 Hz; 1 min
Digital inputs
Nominal voltage
DC
24 V - 250 V
AC
230 V; 50 Hz - 60 Hz
Maximum input voltage
DC
275 V
AC
275 V; 50 Hz - 60 Hz
Minimum reliable activation voltage
DC
19,2 V
AC
80 V; 50 Hz - 60 Hz
Galvanic isolation
AC
3,5 kV; 50 Hz; 1 min
Input current
AC/DC
< 1 mA
Table 116 Technical characteristics of the device.

Table of Contents

Related product manuals