Functionality
USER MANUAL FPC 200 - 3/2017 27
2.2.4.4 Setting parameters
Parameter
Range
Description
Enabled
No
Yes
Enabling protection function.
Operate mode
Off
Definitive time
Enabling protection function separately for each group level.
Pickup value
0,005 0,10 … 2,00 I
n_e
Limit of monitored current.
Trip delay
0,00 2,00 … 300,00 s
Delay of trip signal.
Pickup delay
0 5,00 1000 ms
Time stabilization of fault detection. As a filter of short disturbances on
measuring circuits. Time before protection starts.
Drop-out delay
0,00 … 0,20 … 60,00 s
Time stabilization of pickup signal. Time when the monitored value is
outside the operating range, but the protection does not stop yet.
Drop-out ratio
0,80 0,95 … 1,00 I
p
Drop-out value below which the protection drops.
Pickup block
None
Variable 1
Variable 2
Variable 3
Variable 4
Source of blocking signal.
Table 12: Restricted earth fault function parameters.
2.2.4.5 Counters
Name
Description
Pickup
Total consecutive number of pickup signals.
Trip
Consecutive number of trip signals.
Table 13: Counters presented in restricted earth fault protection.