64 USER MANUAL FPC 200 - 3/2017
2.6.1.14 Parameter table
Parameter
Range
Description
Control settings
Command timeout
0,00 … 0,02 … 1000,00 s
Maximal time of command execution.
CB operation time
0 … 100 … 2000 ms
Time after open or trip command, till CB pole separation.
Command object DI
Source
Local
Remote
Defines the Di command local or remote attribute
Interlocking system
Remote enabled
No
Yes
Disable or enable remote or local operation of CB.
Interlocking MTO
Enabled
No
Yes
Enabling functionality of CB control.
Alarm set
1 … 1000 … 100.000
Consecutive number of trips which triggers an MTO alarm signal.
Block set
1 … 1010 … 100.000
Consecutive number of trips which triggers an MTO block signal.
Interlocking I
2
t
Enabled
No
Yes
Enabling functionality of CB control.
Alarm set
1 … 24000 … 100.000
Consecutive number of trips which triggers an I
2
t alarm signal.
Block set
1 … 30000 … 100.000
Consecutive number of trips which triggers an I
2
t block signal.
Nominal breaking
current of CB
(HMI: CB I
n
break)
0,00 … 0,60 … 50,00 kA
Defined nominal breaking current of CB breaker.
Maximal breaking
current of CB
(HMI: CB I
max
break)
0,00 … 30,00 … 150,00 kA
Defined maximal breaking current of CB breaker.
Number of operations
at nominal breaking
current
(HMI: Opr. At I
n
)
1 … 30.000 … 100.000
Defined maximal number of operations of CB at nominal breaking current.
Number of operations
at maximal breaking
current
(HMI: Opr. At I
max
)
1 … 50 … 100.000
Defined maximal number of operations of CB at maximal breaking
current.
Interlocking Bay
Enabled
No
Yes
Enabling functionality of CB control.
CBFP
Enabled
No
Yes
Enabling functionality of CB control.
Delay
0,00 … 0,2 … 100,00 s
CBFP signal delay. Starts after any trip is present dedicated to open CB.
Ready
Enabled
No
Yes
Enabling functionality of CB control.
Ready value
0
1
State of binary value for which is considered CB is ready
Lockout
Enabled
No
Yes
Enabling functionality of CB control.
Table 56 Parameters of CB control function.