Chapter 6
Controller V6 Touch
DM55 DynaDrum PP V6, Manual No.21-18, Rev.2.19 Page 61
Item Description
1 System 1 Pump 1 is selected.
2
Touch the input box and an Alphabetic Entry Keypad will appear. Enter your desired pump
name and confirm by pressing OK.
The entered pump name will be displayed on the Pump Overview Screen.
3
Press Current Pump Mode to select "Linear Line Speed" or "Pressure Control". Then press the
BACK button to go to the appropriate screen.
4
Automatic Ramp Compensation (ARC) Button
Press to go to the Automatic Ramp Compensation screen.
5
Optional: Minimum Input Pressure
• This field appears only if the pump is configured for a minimum input pressure lock.
• The Minimum Input Pressure is a customer parametrizable value which has to be reached
for the according pumps on decentralized pump (Applicator or Metering Station) to be
released.
• A plausible limit value of Input Pressure (a minimum pressure of not less than 2 bar is
recommended) has to be entered to avoid a dry run of the pumps; otherwise the pump can
6
Pressure Discrepancy Monitor
Check this button if the pressure discrepancy has to be monitored.
7
This is the maximum allowed difference and adjustable between 1-17 bar (15-250 psi).
If actual difference is larger, a discrepancy warning will be generated for reference only.
8
A pressure discrepancy warning can be delayed. This way an excessive difference has to be
present for a minimum time to cause a warning.
9
BACK Button
Press to return to the previous screen.
Extended Pump Mode Settings Screen Example at DM55 with Piston Pump: