Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
207/346
Set-up
UniSAB alarm
Max. pressure
increase 1 min.
[bar]
Flooded
evaporator
Min. suction superheat [K]
ensured by suction superheater
Suction
pressure
[°°C/R]
Suction
pressure
[bara]
< 1K 2K 3K 5K
43 16.9 0.7 2.6 3.0 3.0
44 17.4 0.8 2.7 3.0 3.0
45 17.8 0.8 2.7 3.0 3.0
46 18.3 0.8 2.8 3.0 3.0
Table 46: UniSAB alarm values