Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
229/346
Set-up
6.4.14 Maximum movement of capacity slide
Table 51 is used for the calculation of Manual zero in the Compressor block configuration.
Regulator type
Max. movement
of capacity slide
Evaporating
temp.
R717/R22
Length of
spacer block
Mechanical
zero
Manual zero
SAB 110 SM
84.5 < -20°C 22 No 0%
SAB 110 SF
SAB 110 LM
96 > -20°C None No
*
Factor 0%
SAB 110 LF
SAB 128 HM Mk 2
126
< -20°C 31.5 No 0%
SAB 128 HF Mk 2
SAB 128 HM Mk 3
> -20°C None No
*
Factor 0%
SAB 128 HF Mk 3
SAB 163 M Mk 1, Man Vi
160
< -20°C 38.5 No 0%
SAB 163 F Mk 1, Man Vi
SAB 163 HM Mk 2, Man Vi
SAB 163 HF Mk 2, Man Vi
> -20°C None No
*
Factor 0%
SAB 163 HM Mk 3, Man Vi
SAB 163 HF Mk 3, Man Vi
SAB 163 HM Mk 2, Aut Vi
160
< -20°C 38.5 Yes 24%
SAB 163 HF Mk 2, Aut Vi
SAB 163 HM Mk 3, Aut Vi
> -20°C None No
*
Factor 0%
SAB 163 HF Mk 3, Aut Vi
SAB 202 SM, Man Vi
245 All None
**
No
*
Factor 0%
SAB 202 SF, Man Vi
SAB 202 SM, Aut Vi
SAB 202 SF, Aut Vi
SAB 202 LM, Man Vi
317 All None
**
No
*
Factor 0%
SAB 202 LF, Man Vi
SAB 202 LM, Aut Vi
SAB 202 LF, Aut Vi
SAB 283 L 314
Not
relevant
Not
relevant
Not
relevant
Not
relevant
SAB 283 E 391
SAB 355 L 350
SAB 330 S 262
Not
relevant
Not
relevant
Not
relevant
Not
relevant
SAB 330 L
371
SAB 330 E
480
* If inserting a different value than the default factory set value (0%), the automatic zero setting is eliminated.
Therefore, only insert a value different from 0% after contacting your Sabroe representative.
** If inserting a different value than “No”, the automatic zero setting is eliminated.
Therefore, only insert a value different from “No” after contacting your Sabroe representative.
Table 51: Maximum movement of capacity slide