Engineering manual - UniSAB III 1.10.8
288/346
001930 en 2021.06
UniSAB III (boot) and communication set-up
8.5.4 Configuration of Profibus/DP
See subsection 6.4.6 Communication for the software set-up of the Profibus/DP port in UniSAB III.
First you must enable Profibus communication by setting Profibus to Yes. Next, define the Profibus
Node No. between 1 and 254 and the protocol type or GSD file no. you want to run. GSD file 095D is the
extended protocol and 08AA is the tiny protocol. The communication speed Profi baud rate will be set up
automatically when UniSAB III is connected to another Profibus/DP device.
For more information see the UniSAB Profibus DP protocol manual.