Nominal rating conditions:
Ambient temperature: 77 °F
Max. height above sea level at the place of use: 328 ft
Generator [kVA] 13.0 8.0
Resistive consum‐
ers [kVA]
per phase 6.5 4.0
total 13.0 8.0
Inductive consumers [kW] Rated power 5.0 5.0
Tab. 62 Maximum power supply load
Power reduction at elevated ambient temperatures:
Ambient temperature
[°F]
Generator power
≤86 Full power available
>86 Reduction of 10 % for each temperature rise of 50 °F.
Tab. 63 Power reduction at elevated ambient temperatures
2 Technical Data