3. Check the insulation monitor according to instructions:
Test instructions are provided on the label attached to the generator control box.
DANGER!
Electrical power.
Danger of fatal injury caused by contact with live components!
▶Test the «main circuit breaker» each day while the machine is running.
▶ The generator may only be operated if the main circuit breaker is functioning correctly.
Checking the
safety cut-out
:
➤ Turn on «main circuit breaker» 4
for the generator.
➤ Press and hold the «test button» 3 for 3 seconds.
The «main circuit breaker» 4 trips.
Problem: The «main circuit breaker» does not trip out?
➤ Shut down the generator and call your authorized KAESER service representative.
Tab. 71 Test instructions for a generator with an ground short detection device.
7 Initial Start-up
7.5 Activating the generator
80
Operator Manual Screw Compressor
M100 No.: 9_6999 23 USE