EasyManua.ls Logo

KEB COMBIVERT F6 Series

KEB COMBIVERT F6 Series
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
DEVICE DATA OF THE 400 V DEVICES
Device size
24
Rated switching frequency
2 kHz
Output frequency f
out
/ Hz
0 1.5 3 6 10 25
Frequency-dependent maximum current @ fS
Basic Time Period = 62.5 µs (Parameter is22=0)
I
lim/%
2 kHz 129
142 161
180
180
180
4 kHz 101
112 128
156
179
180
8 kHz 66
73 85
104
123
152
16 kHz 29
32 37
46
54
68
Frequency-dependent maximum current @ fS
Basic Time Period = 71.4 µs (Parameter is22=1)
I
lim/%
1.75 kHz 129
142 161
180
180
180
3.5 kHz 108
119 137
165
180
180
7 kHz 75
83 96
117
137
167
14 kHz 36
40 46
57
67
84
Frequency-dependent maximum current @ fS
Basic Time Period = 83.3 µs (Parameter is22=2)
I
lim/%
1.5 kHz 129
142 161
180
180
180
3 kHz 115
127 145
174
180
180
6 kHz 84
93 107
130
151
180
12 kHz 43
47 54
68
80
99
Frequency-dependent maximum current @ fS
Basic Time Period = 100 µs (Parameter is22=3)
I
lim/%
1.25 kHz 129
142 161
180
180
180
2.5 kHz 122
135 153
180
180
180
5 kHz 92
102 118
143
165
180
10 kHz 54
60 70
86
101
126
Table 19: Frequency-dependent maximum current for device size 24 (2 kHz)
Device size
24
Rated switching frequency
4 kHz
Output frequency f
out
/ Hz
0 1.5 3 6 10 25
Frequency-dependent maximum current @ fS
Basic Time Period = 62.5 µs (Parameter is22=0)
I
lim/%
2 kHz 142
169 180
180
180
180
4 kHz 112
136 156
180
180
180
8 kHz 74
92 107
129
147
174
16 kHz 35
43 49
61
70
84
Frequency-dependent maximum current @ fS
Basic Time Period = 71.4 µs (Parameter is22=1)
I
lim/%
1.75 kHz 142
169 180
180
180
180
3.5 kHz 120
144 165
180
180
180
7 kHz 84
103 119
143
163
180
14 kHz 42
52 60
74
85
102
Frequency-dependent maximum current @ fS
Basic Time Period = 83.3 µs (Parameter is22=2)
I
lim/%
1.5 kHz 142
169 180
180
180
180
3 kHz 127
153 174
180
180
180
6 kHz 93
114 131
157
178
180
12 kHz 49
61 71
87
99
119
Frequency-dependent maximum current @ fS
Basic Time Period = 100 µs (Parameter is22=3)
I
lim/%
1.25 kHz 142
169 180
180
180
180
2.5 kHz 134
161 180
180
180
180
5 kHz 103
125 144
171
180
180
10 kHz 62
76 89
108
123
147
Table 20: Frequency-dependent maximum current for device size 24 (4 kHz)

Table of Contents

Related product manuals