WATER-COOLED DEVICES
Information on coolant management is given in the following
document
www.keb.de/leadmin/media/Techinfo/dr/an/ti_dr_an-liquid-cooling-00004_
en.pdf
NOTICE
Destruction of the heat sink at storage/transport of water-cooled
devices!
Observe the following points when storing water-cooled devices:
► Completely empty the cooling circuit
► Blow out the cooling circuit with compressed air
Destruction of the drive controller due to condensation!
► Use only NC valves!
5.1.6 Permissible volume ow with water cooling
Thevolumeowofthefollowingtablemustbeobserved.
Permissible
volume ow
Max.volumeow Qmax / l /min 15
Table 42: Permissible volume ow with water cooling
NOTICE
Destruction of the heat sink due to erosion !
► Themaximumpermissiblevolumeowmustnotbeexceeded.