CONNECTION OF THE POWER UNIT
4.2.5.2 Terminal block X1A motor connection
Name Function
Terminal connec-
tion
Tightening
torque
Crimp
connector
dimension
type
Max. num-
ber of con-
ductors
1)
U
Motor connection
8 mm stud for
M8 crimp connec-
tor
10...15 Nm
88...132 lb inch
1
For IEC: 2
For UL: 2
V
W
Figure 25: Terminal block X1A motor connection
1)
From 50mm² only one conductor allowed
Crimp connector dimension Type 1
Max. width l / mm 24
Max. shaft length l / mm 46
Max. diameter l / mm 19
Table 32: Crimp connector dimension motor connection
NOTICE
Short circuit due too low air and creepage distances!
The pressing of the crimp connectors must point upwards when
connecting 95 mm² cables!