Remote Interface Reference 3
Status Reporting Commands
E364xA User’s and Service Guide 121
STATus:QUEStionable:INSTrument:ISUMmary<n>:
ENABle <enable value>
Set the value of the questionable instrument Isummary
enable register for a specific output of the two- output power
supply. The particular output must be specified by a
numeric value. n is 1 or 2. 1 selects output1, and 2 selects
output2. This register is a mask for enabling specific bits
from the questionable instrument Isummary event register to
set the Instrument Summary bit (bits 1 and 2) of the
questionable instrument register. These bits 1 and 2 are the
logical OR of all the questionable instrument Isummary event
register bits that are enabled by the questionable instrument
Isummary enable register.
STATus:QUEStionable:INSTrument:ISUMmary<n>:
ENABle?
Query the value of the questionable instrument Isummary
enable register. n is 1 or 2.
*CLS
Clear all event registers and Status Byte register.
*ESE <enable value>
Enable bits in the Standard Event Enable register. The
selected bits are then reported to the Status Byte.
*ESE?
Query the Standard Event Enable register. The power supply
returns a decimal value which corresponds to the
binary- weighted sum of all bits in the register.
*ESR?
Query the Standard Event register. The power supply returns
a decimal value which corresponds to the binary- weighted
sum of all bits in the register.