EasyManua.ls Logo

Kidde Fire Systems ARIES NETLink

Kidde Fire Systems ARIES NETLink
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Networking
February 2012 5-14 P/N 06-237058-001
Figure 5-10. Typical Remote Alarm-Verification Message Display
The following actions also occur when a control unit is configured as Group 0 or when the alarm-
verification event is either from another control unit in the same group as the control unit or from
any other control unit in a network configured for global operation.
1. The internal buzzer pulses
2. The alarm-verification event is stored in the event log
3. The alarm-verification message is transmitted to peripheral devices such as RDCMs, if
applicable
4. The alarm-verification message is communicated via the NIC and RS-232 ports, as
applicable
Refer to Section 4-10.3.6 for what to do when a remote alarm-verification message is received.
Note: The time remaining on the alarm-verification timer will only appear on the display of the
control unit that received the verification report from the smoke detector. Remote, networked
control units will not display the alarm-verification timer.
5-8.11 Remote Supervisory Events
Remote supervisory events from a networked control unit are shown in the upper line of the LCD
display by:
Node-of-origin
Device address
State change
Device type
The lower line indicates the up-to-40-character message assigned to the device using the ARIES
NETLink configuration program.
N:04 L1:010 VERIFY ON PHOTOELECTRIC
CONTROL ROOM
Alarm-Verification Indication On
(Smoke Detectors only)
Device Type Reporting
Alarm-Verification On
Node Number
Device Address L1:010
Device-Specific
Custom Message

Table of Contents

Related product manuals