February 2012 1-26 P/N 06-237058-001
1-16 HIGH SENSITIVITY SMOKE DETECTORS
Table 1-5. Supported High Sensitivity Smoke Detectors
ORION XT
®
The ORION XT High Sensitivity Smoke Detector is
designed for early warning smoke detection
applications such as telecommunications facilities,
data processing rooms, museum, warehouses and
cleanrooms. The ORION XT consists of a laser
particle counter detector head, a high efficiency fan
module and a termination board. When connected
to an air sampling pipe network, the detector
provides coverage for an area up to 20,000 square
feet.
An ORION XT can be connected to the Signaling
Line Circuit using a PEGAsys
TM
Addressable Loop
Module (PALM), P/N 77-297103-000, which mounts
inside the detector housing. (Refer to Section 1-17,
SmartOne Addressable Modules.)
AIR-Intelligence
ASD-160H
The AIR-Intelligence
TM
ASD-160H is a highly
sophisticated “next generation” detector that
provides high sensitivity smoke detection with very
early warning. The ASD-160H incorporates a
patented “artificial intelligence” known as
ClassiFire®, which allows the detector to configure
itself to optimum sensitivity, alarm thresholds, and
minimum nuisance alarms for various
environments. The ASD-160H offers protection for
an air sampling pipe network up to 164 feet (50
meters) total.
An ASD-160H can be connected to the Signaling
Line Circuit using an Addressable Protocol Interface
Card (APIC), P/N 74-333001-001, which mounts
inside the detector housing. Up to 127 AIR-
Intelligence detectors can be networked together
using an AIR-Intelligence Command Module.
AIR-Intelligence
ASD-320
The AIR-Intelligence ASD-320 is identical to the
ASD-160H detector but offers protection for a larger
air sampling pipe network up to 328 feet (100
meters) total.
An ASD-320 can be connected to the Signaling Line
Circuit using an Addressable Programmable
Interface Card (APIC), P/N 74-333001-001, which
mounts inside the detector housing. Up to 127 AIR-
Intelligence detectors can be networked together
using an AIR-Intelligence Command Module.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems ARIES NETLink and is the answer not in the manual?

Kidde Fire Systems ARIES NETLink Specifications

General IconGeneral
BrandKidde Fire Systems
ModelARIES NETLink
CategoryControl Unit
LanguageEnglish

Related product manuals