P/N 06-237058-001 1-27 February 2012
1-17 SMARTONE ADDRESSABLE MODULES
SmartOne addressable modules are of four general types:
Monitor Modules: These modules provide a uniquely-identifiable interface between the ARIES
NETLink and an initiating device.
Relay Module: This module supplies an unpowered, Form-C contact at a point-specific address.
Control Modules: These modules provide a uniquely-identifiable interface between the ARIES
NETLink and conventional notification appliances such as horns and strobes.
Remote Releasing Modules: These modules provide the ability to remotely activate extinguishing-
system control devices (i.e., electro-explosive actuators and solenoid valves).
AIR-Intelligence
ASD-640 /
AIR-Intelligence
Command Module
The AIR-Intelligence ASD-640 is identical to the
ASD-160H detector but offers protection for an even
larger air sampling pipe network up to 656 feet (200
meters) total.
An ASD-640 can be connected to the Signaling Line
Circuit using an Addressable Protocol Interface
Card (APIC), P/N 74-333001-001, which mounts
inside the detector housing. Up to 127 AIR-
Intelligence detectors can be networked together
using an AIR-Intelligence Command Module.
Table 1-6. Supported SmartOne Addressable Modules
Device Description Illustration
SmartOne Addressable
Monitor Module,
Model AI
The Model AI Addressable Monitor Module is used to
monitor conventional, unpowered, contact-type
initiating devices through a CLASS-B, Style-B initiating
device circuit. Two styles of AIs are available: P/N 70-
4070X8-001 (N.O.) for interfacing to normally-open,
contact devices such as, abort stations, manual
stations, waterflow switches, and supervisory switches
and P/N 70-407018-002 (N.C.) for use within control
equipment providing the normally closed trouble
contact, such as older-style supervisory switches. The
Normally Closed AI Module, P/N 70-407018-002, is not
considered to be an initiating device circuit.
The AI Module is designed to be mounted in the
electrical box of the device being monitored.
SmartOne Addressable
AlarmLine Module,
Model AAM
The Model AAM Addressable AlarmLine Module is
a monitor module that enables an AlarmLine
sensor cable to report pre-alarm and alarm or
overheat events, and trouble signals to the ARIES
NETLink through the signaling line circuit. The
AAM, P/N 73-100001-003, is equipped with a metal
cover plate for mounting to a 4” square electrical
box. P/N 73-100003-001, is a surface-mount,
NEMA-4 enclosure for the AAM.
Table 1-5. Supported High Sensitivity Smoke Detectors
MODEL AI, N/O
INSTRUCTIONS
SEE INSTALLATION
CAT. NO. 70-407008-001
SmartOne
TM
FOR SERVICE SEND TO:
KIDDE-FENWAL, INC.
400 MAIN ST.
ASHLAND, MA 01721
DATE OF MANUFACTURE:
MAX. INSTALL. TEMP. 120°F
7654321
06-235578-001
PC PC PC PC
(+) (-) (+) (-)
8
A
SW
B
SW
(+)
LED
(-)
LED
ALL TERMINALS ARE POWER LIMITED
TM