FM Rules for Preaction/Deluge Systems
P/N 06-237058-001 D-1 February 2012
APPENDIX D
FM RULES FOR PREACTION/DELUGE SYSTEMS
ARIES NETLink applications which require Factory Mutual (FM) approved Pre-Action and/or Deluge
Systems must conform to the following guidelines:
Detection Zone 1 (Det1), Detection Zone 2 (Det2) and Waterflow (W'Flow) Initiating Circuits must
be configured for CLASS-A, Style D wiring.
The Battery backup system must provide for 90 hours of Standby operation followed by 10
minutes of Alarm operation. Refer to Appendix A for calculations.
The Agent Release Output must be configured for Deluge Solenoid activation. The Solenoid
Activation Time must be set either for:
–10 minutes, or
–15 minutes, or
On-until-reset.
The wiring connection of the control unit to the Deluge Solenoids must be as detailed in the
Installation section of this manual.