Networking
February 2012 5-24 P/N 06-237058-001
3. Select the local node by pressing the <Enter> Key, or enter a remote node number then press
the <Enter> Key. The top-level menu selections will be displayed.
Figure 5-36. Top-Level Menu Selection
4. Press the 3 Key to select the Set sub-menu.
Figure 5-37. Set Sub Menu
5. Press the 4 Key to select PROGRAMMING
Figure 5-38. Additional Set Menu Options
6. Press the <Scroll> Key once and then press the 9 Key to select RESYNCH NETWORK.
Figure 5-39. Resynch Network Option
7. The display will indicate the following; press backspace to exit from the menus.
Figure 5-40. Resynch Network Display
8. Press the <Backspace> Key multiple times as required to exit from the Menu State.
The events being displayed on the control unit will now be consistent with the events being displayed
on all of the networked control units.
1: ISOLATE 2: LIST
3: SET 4: TEST
1: TIME/DATE 2: PORT CONTROL
3: SLC DEVICES 4: PROGRAMMING
5: GLOBALS 6: OUTPUTS/BACKPLANE
7: CONTROL MODULES 8: NETWORK
1: DAY/NIGHT 2: PASSWORDS
3: SLC AUTOLEARN 4: AUTOSETUP
5: ALM VERIFICATION 6: POSITIVE ALM SEQ
7: CLEAR EVENTS SCROLL for more
8: CLEAR TESTS 9: RESYNCH NETWORK *
NETWORK EVENT RESYNCHRONIZATION
MESSAGE SENT, PRESS BACKSPACE TO EXIT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems ARIES NETLink and is the answer not in the manual?

Kidde Fire Systems ARIES NETLink Specifications

General IconGeneral
BrandKidde Fire Systems
ModelARIES NETLink
CategoryControl Unit
LanguageEnglish

Related product manuals