August 2013 3-18 P/N 06-236530-001
3-2.5.2.2.10 How to Globally De-Isolate Initiating Devices
Purpose: To enable the ARIES Control Unit to process initiating and
trouble signals from all previously-isolated SLC-based and IIM-based
initiating devices
3-2.5.2.2.11 How to Globally Isolate System Outputs
Purpose: To prevent all SLC-based and control-unit-based outputs
(including relays) from being activated by the ARIES Control Unit
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select "Global Isolate" option
6 Press 1 Key and then press "Enter" Key to confirm
selection.
Select “Inputs”
7 Press 2 Key and then press "Enter" Key to confirm
selection.
Execute De-Isolation Routine for all initiating
devices
8 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select "Global Isolate" option
6 Press 2 Key and then press "Enter" Key to confirm
selection.
Select “Outputs”
7 Press 1 Key and then press "Enter" Key to confirm
selection.
Execute Isolation Routine for all output devices
and circuits
8 Press "Backspace" Key (as required) Exit Menu System
9 Press "Acknowledge" Key Silence buzzer and change Supervisory LED from
flashing to steady