P/N 06-236530-001 3-17 August 2013
3-2.5.2.2.8 How to De-Isolate Remote-Annunciator Modules
Purpose: To enable previously-isolated remote-annunciator modules
to display messages or to execute activation instructions issued by the
ARIES Control Unit.
3-2.5.2.2.9 How to Globally Isolate Initiating Devices
Purpose: To prevent initiating and trouble signals from all SLC-based
and IIM-based initiating devices from being processed and acted upon
by the ARIES Control Unit
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press 3 Key Select "Control Modules" option
5 Press 1 Key for ATMs or
Press 2 Key for RDCMs
Press "Enter" Key to confirm selection.
Select module to de-isolate
6 Use keypad to enter module to de-isolate.
Press "Enter" Key to confirm selection.
Execute De-Isolation Procedure for module
7 Press 2 Key Select De-Isolation Routine
8 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select "Global Isolate" option
6 Press 1 Key and then press "Enter" Key to confirm
selection.
Select “Inputs”
7 Press 1 Key and then press "Enter" Key to confirm
selection.
Execute Isolation Routine for all initiating devices
8 Press "Backspace" Key (as required) Exit Menu System
9 Press "Acknowledge" Key Silence buzzer and change Supervisory LED from
flashing to steady