EasyManua.ls Logo

Kidde ARIES

Kidde ARIES
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P/N 06-236530-001 3-17 August 2013
3-2.5.2.2.8 How to De-Isolate Remote-Annunciator Modules
Purpose: To enable previously-isolated remote-annunciator modules
to display messages or to execute activation instructions issued by the
ARIES Control Unit.
3-2.5.2.2.9 How to Globally Isolate Initiating Devices
Purpose: To prevent initiating and trouble signals from all SLC-based
and IIM-based initiating devices from being processed and acted upon
by the ARIES Control Unit
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press 3 Key Select "Control Modules" option
5 Press 1 Key for ATMs or
Press 2 Key for RDCMs
Press "Enter" Key to confirm selection.
Select module to de-isolate
6 Use keypad to enter module to de-isolate.
Press "Enter" Key to confirm selection.
Execute De-Isolation Procedure for module
7 Press 2 Key Select De-Isolation Routine
8 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 4 Key Select "Global Isolate" option
6 Press 1 Key and then press "Enter" Key to confirm
selection.
Select “Inputs”
7 Press 1 Key and then press "Enter" Key to confirm
selection.
Execute Isolation Routine for all initiating devices
8 Press "Backspace" Key (as required) Exit Menu System
9 Press "Acknowledge" Key Silence buzzer and change Supervisory LED from
flashing to steady

Table of Contents

Related product manuals