August 2013 3-16 P/N 06-236530-001
3-2.5.2.2.6 How to De-Isolate High-Sensitivity Smoke Detectors (HSSDs)
To enable initiating and trouble signals from previously-isolated HSSDs
connected to an IIM to be processed and acted upon by the ARIES
Control Unit.
3-2.5.2.2.7 How to Isolate Remote-Annunciator Modules
Purpose: To prevent selected remote-annunciator modules from
displaying messages or from carrying out activation instructions issued
by the ARIES Control Unit.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 7 Key Select "HSDs" option
6 Use keypad to enter single HSSD or range of
HSSDs to de-isolate. Press "Enter" Key to confirm
selection
Get prompt to Isolate or De-Isolate
7 Press 2 Key and then press "Enter" Key to confirm
selection.
Execute De-Isolation Routine for single HSSD or
range of HSSDs entered in Step 6.
8 Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press 3 Key Select "Control Modules" option
5 Press 1 Key for ATMs or
Press 2 Key for RDCMs
Press "Enter" Key to confirm selection.
Select module to isolate
6 Use keypad to enter module to isolate.
Press "Enter" Key to confirm selection.
Execute Isolation Procedure for module
7 Press 1 Key Select Isolation Routine
8 Press "Backspace" Key (as required) Exit Menu System
9 Press "Acknowledge" Key Silence buzzer and change Supervisory LED from
flashing to steady