August 2013 3-68 P/N 06-236530-001
3-2.5.2.4.48 How to Enable a Networked Control Unit to be Remotely Reset by
Another Control Unit
Purpose: To allow a networked control unit to be remotely reset by
other control units in the network. This procedure enables the control
unit to be reset as follows:
1. By any other control unit when no sub-groups are used
2. By any other control unit in its group when sub-groups are used
3. By the master mode (i.e., Group 0)
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 6 Key Select "Network" option
6 Press "Scroll" Key Access additional options
7 Press 5 Key Select "Reset"
8 Press 1 Key and then press "Enter" Key to confirm
selection.
Select "Enable"
9 Press "Backspace" Key (as required) Exit Menu System
10 Wait until "Initializing Configuration" message
disappears from the display.
Initialization complete