August 2013 3-70 P/N 06-236530-001
3-2.5.2.4.50 How to Enable Outputs on a Networked Control Unit to be Remotely
Silenced by Another Control Unit
Purpose: To allow the silenceable outputs on a networked control unit
to be silenced by other control units in the network. This procedure
enables the outputs to be silenced as follows:
1. By any other control unit when no sub-groups are used
2. By any other control unit in the group when sub-groups are used
3. By the master mode (i.e., Group 0)
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 6 Key Select "Network" option
6 Press "Scroll" Key Access additional options
7 Press 6 Key Select "Silence"
8 Press 1 Key and then press "Enter" Key to confirm
selection.
Select "Enable"
9 Press "Backspace" Key (as required) Exit Menu System
10 Wait until "Initializing Configuration" message
disappears from the display.
Initialization complete