P/N 06-236530-001 3-71 August 2013
3-2.5.2.4.51 How to Prevent the Outputs on a Networked Control Unit from Being
Remotely Silenced by Another Control Unit
Purpose: To prevent the silenceable outputs on a networked control
unit from being silenced by other control units in the network. This
procedure restricts silencing of the outputs to the control unit itself.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 6 Key Select "Network" option
6 Press "Scroll" Key Access additional options
7 Press 6 Key Select "Silence"
8 Press 2 Key and then press "Enter" Key to confirm
selection.
Select "Disable"
9 Press "Backspace" Key (as required) Exit Menu System
10 Wait until "Initializing Configuration" message
disappears from the display.
Initialization complete