P/N 06-236530-001 3-79 August 2013
3-2.5.2.4.64 How to Register High-Sensitivity Smoke Detectors (HSSDs)
Purpose: To inform the ARIES Control Unit of the quantity and
addresses of the HSSDs that will be connected to the IIM.
Note: The HSSDs are also automatically registered when included
with the IIM in a configuration upload via the ARIES
Configuration Program.
CAUTION
This Registration Procedure shall not be used to configure the HSSDs. This is
primarily a procedure to store these detectors in the ARIES's configuration
memory. The HSSDs shall be configured with the LaserNET Configuration
Program.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password Gain access to menus
3 Select the local node then press “Enter” or a
select a remote node number, press “Enter” then
enter the remote node’s password.
Access applicable control unit (if networked
system)
4 Press 3 Key Enter Set-Menu branch
5 Press "Scroll" Key twice Access additional options
6 Press 8 Key Select "HSDs" option
7 Press 3 Key Select register HSDs
8 Use keypad to enter single HSSD or range of
HSSDs to register.
Press "Enter" Key to confirm selection.
Specify single HSSD or range of HSSDs to be
registered
9 Press "Backspace" Key (as required) Exit Menu System
10 Wait until "Initializing Configuration" message
disappears from the display.
Initialization complete