P/N 06-236530-001 3-87 August 2013
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 4 Key Enter Test-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 6 Key Select "Alarm Simulation Test"
6 Use keypad to enter initiating device to report
"alarm off."
Press "Enter" Key to confirm selection.
Specify device to issue "alarm-off" message
7 Press 0 Key and Press “Enter” Key Initiate "alarm-off" message
8 Press "Acknowledge" Key Make Alarm LED flash steadily
9 Repeat Steps 6 to 8 (as required) Report "alarm-off" for all simulated initiating
devices
10 Press "Backspace" Key (as required) Exit Menu System
11 Press "Reset" Switch Return to Normal Operating Condition