August 2013 5-10 P/N 06-236530-001
Addr Duplicate Address Fault On There is more than one SLC device
with address Addr. Refer to
Paragraph 3-2.5.2.5.20
• Find all devices with rapidly-pulsing
LEDs. Monitor modules require an
external LED to be installed.
• Check the approved layout drawing
for the correct address
corresponding to each device
location
• Remove the incorrectly-addressed
device(s) and re-address with the
Handheld Programmer. Refer to
Appendix D. Alternatively,
• Remove the correctly-addressed
device and all but one incorrectly-
addressed device. Use the
procedure in Paragraph 3-2.5.2.4.6
to change the incorrect device
address.
• Add one more incorrectly-
addressed device and re-address
using the procedure in
Paragraph 3-2.5.2.4.6. Repeat as
necessary until all incorrectly-
addressed devices have been
correctly addressed.
• Reconnect the original correctly-
addressed device
Addr EEPROM Fault ON The device at address Addr is
reporting an internal software fault
• Replace the device
Addr High Airflow On ORION-XT
Interface Module
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by
a PALM. Excessively high air flow
through the piping system
• Look for leaks in the HSSD's piping
system
• Use OCS to troubleshoot the HSSD.
The airflow may need to re-
normalized.
• Refer to ORION-XT Installation,
Operation, and Maintenance
Manual, P/N 89.200.
Addr Input Trouble On Monitor
Module
An open circuit in a monitor module's
initiating device circuit
• Refer to AI Installation Instructions,
P/N 06-235578-001.
• Look for discontinuity in initiating
device circuit.
• Check for missing 10k end-of-line
resistor.
Table 5-3. SLC Events (Continued)
SLC Events
Error Message Probable Cause Corrective Action