P/N 06-236530-001 5-9 August 2013
Addr Communication Fault On A loss of communications between
the SLC's driver circuit and the
device at address Addr.
Check device connections to wiring
Ensure that device has not been
removed
Check SLC wiring for excessive
capacitance and/or resistance if the
device LED is blinking. Refer to
Paragraph 2-8.1. Rewire using
recommended wire in Appendix B.
Replace the device if above
procedures are unsuccessful.
Addr Detector Tbl On ORION-XT
Interface Module
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by
a PALM
• Check the PALM-to-HSSD
connections
• Use OCS to troubleshoot the HSSD.
• Refer to ORION-XT Installation,
Operation, and Maintenance
Manual, P/N 89.200.
Addr Drift Fault On Device Type The inability of a SmartOne smoke
detector to further compensate for
reference signal variation
• Globally isolate all outputs. See
Paragraph 3-2.5.2.2.9.
• Disconnect smoke detector from
SLC and visually inspect for
damage. Clean the detector as
recommended.
• Use Handheld Programmer to test
the device. Refer to Appendix D.
Reconnect device to SLC.
• Measure the detector sensitivity.
See Paragraph 3-2.5.2.3.6.
Replace the detector if the clean-
air reference value is more than
one half of the alarm-threshold
value.
• Conduct an initiating device test on
the detector. See
Paragraph 3-2.5.2.5.1.
• Activate and confirm a proper
alarm response from the detector.
• Replace device if any of above tests
is unsuccessful.
• Globally de-isolate all outputs. See
Paragraph 3-2.5.2.2.9.
Table 5-3. SLC Events (Continued)
SLC Events
Error Message Probable Cause Corrective Action