Listed and Approved Releasing Devices
P/N 06-236530-001 C-3 August 2013
Figure C-2. Agent Release Circuit Wiring - Initiators, Non-Power-Limited
Note: 1. Polarities must be observed.
2. Must be close nippled to Solenoid enclosures.
3. The ARC is Non-Power-Limited when in-line device not used.
4. Route Non-Powered-Limited wiring at least 1/4-inch away from all Power-Limited
wiring. Do not attach Power-Limited wiring to the same terminal block.
5. When using initiators, different types of initiators must NOT
be mixed on the same
circuit. The limiting resistor is used to make the total circuit resistance equal to ±
1 ohm. The resistor must have a rating of 1 watt minimum.
6. Control Head P/Ns 90-487100-001, 87-120099-001, and 87-120099-002 when used
with the panel must include Solenoid P/N 83-100034-001 and Microswitch P/N 87-
120039-001.
C-4 UL LISTED AND FM APPROVED ASSEMBLY
The following actuator assembly is UL Listed and FM Approved.
Table C-4. UL Listed and FM Approved Actuator Assembly
Part Number Max. No. per Release Ckt. Max. Rel. Ckt. Resistance
83-131025-001 1 3 ohms
TB14 OR TB15
10 OHM LIMITING
RESISTOR
MAXIMUM WIRE RESISTANCE: 3 OHMS
R1+
R1-
R2-
R2+
MAXIMUM CURRENT UNDER
FAULT CONDITIONS: 5A
INITIATOR