August 2013 3-14 P/N 06-236530-001
3-2.5.2.2.2 How to De-Isolate SLC Devices
Purpose: To enable the ARIES Control Unit to process initiating and
trouble signals from previously-isolated SmartOne automatic detectors
and monitor modules. Also to enable previously-isolated SmartOne
control and relay modules to execute activation instructions issued by
the ARIES Control Unit.
3-2.5.2.2.3 How to Isolate Control-Unit-Based Outputs
Purpose: To prevent selected control-unit-based outputs from carrying
out activation instructions issued by the ARIES Control Unit.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press 1 Key Select "SLC Devices" option
5 Press 1 Key for SLC inputs or 2 Key for SLC
outputs.
Press "Enter" Key to confirm selection.
Select “SLC Inputs” or “SLC Outputs.”
6Use keypad to enter single device or range of
devices to isolate.
Press "Enter" Key to confirm selection.
Get prompt to Isolate or De-Isolate
7 Press 2 Key and then press "Enter" Key to confirm
selection.
Execute De-Isolation Routine for single device or
range of devices entered in Step 6.
Press "Backspace" Key (as required) Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 1 Key Enter Isolate-Menu branch
4 Press 2 Key Select "Outputs" option
5 Press 1 Key for NACs or
Press 2 Key for Release Circuits or
Press 3 Key for Combo Circuits
Press 4 Key for Relays
Select output to isolate
6 Use keypad to enter single output or range of
outputs to isolate.
Press "Enter" Key to confirm selection.
Get prompt to Isolate or De-Isolate
7 Press 1 Key and then press "Enter" Key to confirm
selection
Execute Isolation Routine for single output or
range of outputs entered in Step 6.
8 Press "Backspace" Key (as required) Exit Menu System
9 Press "Acknowledge" Key Silence buzzer and change Supervisory LED from
flashing to steady.