Chapter 2: Front panel programming
P/N 3102352-EN • REV 005 • ISS 28DEC18 103
Option
Description
Rings to answer
Set rings to answer to Off or 1 to 15 rings. Specifies how many rings before
the dialer answers incoming calls.
Ring type
Set ring type to Any or Normal. Specifies the type of ring expected when an
incoming call is received.
Callback
Select Enabled or Disabled to enable or disable callback security. With
callback security enabled, the dialer will answer an incoming call, and then
hang up and redial the callback number in an attempt to connect to the PC
running the configuration utility. Use this feature to increase security and to
limit your connect to only the PC at the preprogrammed number.
Callback number
Enter the callback phone number (up to 20 digits). This specifies the phone
number that is used for call back.
Note: Select Off to set to 0 wait time, no frequencies, or no occurrence.
To program the dialer:
1. Display the panel configuration options menu. See “Panel programmingon page 95.
2. Choose CMS Device.
3. Choose Dialer.
4. Program the dialer using Table 35 on page 101. For dialer default settings, see “Factory
default settingson page 41.
5. When you have finished programming each option, choose Save.
6. Press the Menu button to exit menu mode, or continue programming.
CMS network (transmitter) programming
Note: Connecting to a central monitoring station (CMS) using a TCP/IP Ethernet network does
not comply with CAN/ULC S559 3
rd
edition requirements.
The information programmed here pertains to the central monitoring station (CMS) network
that the control panel uses to communicate with the CMS. This is a TCP/IP Ethernet network.
Event information is sent to the CMS just as it is when using a dialer; however, the
transmission is over an Ethernet network rather than the telephone lines.
To program the panel for network reporting, you must install and enable the optional SA-ETH
Ethernet module. Once installed, program only the network card connected to a compatible
network receiver, as listed in the appropriate compatibility guide.
Obtain the following information from the central monitoring station’s network administrator:
An IP address
Port number
Receiver number
Line number