Chapter 2: Front panel programming
102 P/N 3102352-EN • REV 005 • ISS 28DEC18
Option
Description
Secondary receiver number
Format
Send restorals
Retry time seconds
Retry count
Event notification
CID: Contact ID is the alarm format that the monitoring facility's Digital Alarm
Communicator Receiver (DACR) will receive. SeeDefault contact ID event
codeson page 45.
Set send restorals to:
Yes: Sends off-normal event restorals to the monitoring facility DACR.
Required setting for UL/ULC installations. SeeUL/ULC programming
requirementson page 34 for details.
No: Does not send off-normal event restorals to the monitoring facility DACR
Set retry time to 1 to 45 seconds. Specifies the wait time between each time
the dialer attempts a connection to the DACR. See “UL/ULC programming
requirementson page 34 for details.
Set the retry count to 5 to 10 attempts. Specifies how many times the dialer
will attempt to call the DACR before timing out.
Set event notification (event reporting) to:
Device: Only device information is reported or transmitted, no zone
information. This setting uses device event notification settings for reporting
events. Make sure your device event notification settings are correct. See
Central monitoring station device programmingon page 99.
Zone: When a device is a member of a zone, only the zone information is
reported or transmitted. Device information is not reported or transmitted.
This setting uses zone event notification settings for reporting events. Make
sure the zone event notification settings are correct. See “Loop event
programmingon page 112.
Event: Only the event type (alarm, supervisory, trouble, etc.) is reported or
transmitted, no device or zone information. This setting uses the CMS event
notification settings for reporting events. Make sure the event notification
settings are correct. See “Central monitoring station device programmingon
page 99.
Line 1 and 2
Dialing:
Cut duration/supervision
Program line 1 options, and then program line 2 options. When you have
finished programming each line, choose Save.
Select Tone or Pulse dialing.
Set the cut duration/supervision to Off or 10 to 120 seconds. Specifies the
length of time a phone line trouble is detected before reporting the trouble.
Tone wait seconds
Set tone wait to Off or 1 to 30 seconds. Specifies how long the dialer waits to
get a dial tone.
Call disconnect seconds
Set call disconnect to Off or 1 to 45 seconds. Specifies the length of time the
dialer seizes the line (to disconnect parallel devices) before attempting to dial
out.
Test frequency
hours Set test frequency to 0 to 240 hours. Specifies how often the dialer performs
a test call. The default setting is 6 hours to comply with agency requirements.
See “UL/ULC programming requirementson page 34 for details.
Test
time Set the test time to the desired time of day for running the test.