Parameter setting with the XT EMZ9371BC keypad
Commissioning example in V/f characteristic control mode
6.3
6.3.1

6.3−3
EDSVF9383V EN 7.1−04/2012
NoteSwitch−on sequence
18. Set your type of the speed feedback system
"Feedback type" (C0025)
Lenze setting: 1 (no feedback)
See chapter "Commissioning" ®
"Setting of speed feedback"
A When using a TTL encoder:
Select the encoder used under C0025
B When using a TTL encoder with a number of
increments which cannot be set under C0025:
Set C0025 = 100
Enter the number of increments under C0420
C If required, compensate a voltage drop in the
incremental encoder cable. Use C0421 to adjust the
supply voltage for the TTL encoder.
D When using a HTL encoder:
Set C0025 = 101
Enter the number of increments under C0420
19. Set the maximum speed (C0011)
Lenze setting: 3000 rpm
0 %
[n]
100%
C0011
C0010
See chapter "Commissioning" ®
"Acceleration, deceleration, braking,
stopping"
20. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
 +t
ir
@
C0011
f
2
* f
1
(see chapter "Commissioning" ®
"Acceleration, deceleration, braking,
stopping")
21. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
 +t
if
@
C0011
f
2
* f
1
(see chapter "Commissioning" ®
"Acceleration, deceleration, braking,
stopping")
22. If required, set the quick stop deceleration ramp
(C0105)
Lenze setting: 5.00 s
See chapter "Commissioning" ®
"Acceleration, deceleration, braking,
stopping"
23. If required, adapt the fixed setpoints JOG. See code table
A JOG 1 (C0039/1)
Lenze setting: 1500 rpm
Activation:
X5/E3 = HIGH
B Further fixed setpoints:
JOG 2 (C0039/2) ... JOG 15 (C0039/15)
24. Ensure a powerfail−proof saving of the settings in
one of the four parameter sets (C0003)
Use C0003 = 1 to save the settings in parameter
set 1.
Code C0003 is the first code in the
menu "Setup V/f".
After switching on the DC 24 V supply
or mains connection, parameter set 1 is
automatically activated.
(see chapter "Parameter setting")
25. Switch on the mains if the external DC 24 V supply
voltage is switched on only.
26. Enable controller
misc009
59 28
X5
}
Terminal X5/28 = HIGH
(see chapter "Commissioning"
®"controller inhibit")
27. Enter the setpoint
Analog setpoint
selection:
−10 ... +10 V via
potentiometer at X6/1
and X6/2
Fixed speed:
Activate JOG 1 with
X5/E3 = HIGH
JOG 1 is parameterised in C0039/1