Page 54
©2013 Technical Marine Service, Inc. LC-100 V2.97
Programming Horn Output
1. Enter Program Mode by pressing the MENU key.
2. At SYSTEM press the UP or DOWN keys to scroll to OUTPUTS.
3. Press ENTER. The unit will display LIGHTS.
4. Press the DOWN key. The unit will display HORN.
5. Press ENTER. The unit will display HI HI.
6. Select those alarms you wish to activate the horn by pressing the MENU key. An asterisk
(*) will appear to the right of the display indicating the alarm has been selected.
7. Press ENTER to save the selected alarms. SAVING will appear briefly on the display and
the display will return to HORN indicating the selections have been recorded.
8. Press ESCAPE to return to normal operation.
Relay Outputs
The LevelCom 100 has two optional “Form C” relay outputs. These relay outputs allow the
user to configure the LevelCom 100 to activate external operations, such as, alarms, motor
controls, etc. If you have ordered relay outputs then the LevelCom 100 will display RELAY 1
and RELAY 2 under the Outputs section of the program (Please refer to the Configuration
Flow Chart).
The relays can be programmed to be either alarm or control outputs. If relays are configured
as alarm outputs, they will function similarly to the light or horn outputs. The relays differ
from the lights and the horn in that they do not normally respond to the ACK button. They
normally activate when the alarm condition occurs, and clear at the assigned hysteresis level.
Relays cannot be configured to latch. As alarm outputs the relays are intended for
interfacing the LevelCom 100 to existing alarm systems.
It is possible to configure an alarm relay to be locally acknowledged. In this case the relay
will respond to the ACK button. This setup can be used to build a local alarm system for a
group of LevelCom 100s. The relay outputs from each LevelCom 100 can be paralleled to
run an alarm horn. To silence the horn, the ACK button must be pressed on the LevelCom
100 which is generating the alarm.
When a relay is configured as a System Failure relay, it will respond only to failure
conditions, such as Sense Line Plugged, Sense Line Leak, and so on.