Page 58
©2013 Technical Marine Service, Inc. LC-100 V2.97
13. Press the UP or DOWN keys to scroll to the Off Setpoint you have defined on your
worksheet.
14. Press ENTER. SAVING will appear briefly on the display and the display will shift to ON
SETPOINT.
Analog Output
The optional analog output module gives the LevelCom 100 a 4 – 20 mA output capability.
The output can function either as a gauge output to remotely indicate depth, volume, or
weight to a remote meter, or data acquisition system. If the LevelCom 100 has the auto
specific gravity option installed the analog output can also function as a specific gravity
gauge output.
It is also possible to configure the analog output as a control output. In this case there are 4
adjustable parameters to configure the output value. The Minimum Current is a value
between 4 mA and 20 mA. The maximum current is a value between the minimum current
value and 20 mA. The Minimum Current Setpoint is the depth where the output signal takes
the minimum value. The Maximum Current Setpoint is the depth where the output signal
takes the maximum value. This gives great flexibility in the configuration of the analog
output.
If the Minimum Current Setpoint is below the Maximum Current Setpoint, the current will be
at the Minimum Current value when the level is below the Minimum Current Setpoint. The
output will vary smoothly from the Minimum Current value to the Maximum current value
when the level is between the setpoints. When the level is above the Maximum Current
Setpoint, the output current will remain at the Maximum Current value.
If the Minimum Current Setpoint is above the Maximum Current Setpoint, the current will be
at the Maximum Current value when the level is below the Maximum Current Setpoint. The
output will vary smoothly from the Maximum Current value to the Minimum current value
when the level is between the setpoints. When the level is above the Minimum Current
Setpoint, the output current will remain at the Minimum Current value.
Configure as a Gauge Output
1. Enter Program Mode by pressing the MENU key.
2. At SYSTEM press the UP or DOWN keys to scroll to OUTPUTS.
3. Press ENTER. The unit will display LIGHTS.
4. Press the DOWN key until unit displays ANALOG OUTPUT.
5. Press ENTER. The unit will display GAUGE.