Programming Relay Outputs
Note: The following procedure applies to both relay outputs. Follow the same procedure for
Relay 2.
Alarm Relay Configuration
Follow these instructions to set up a relay for ALARM or SYS FAIL operation.
1. Enter Program Mode by pressing the MENU key.
2. At SYSTEM press the UP or DOWN keys to scroll to OUTPUTS.
3. Press ENTER. The unit will display LIGHTS.
4. Press the DOWN key until unit displays RELAY 1.
5. Press ENTER. The unit will display ALARM.
6. Press the UP or DOWN keys to scroll to ALARM, or SYS FAIL .
7. Press MENU to select the function of the relay. An asterisk (*) will appear to the right of
the display indicating the function has been selected. Also select LOCAL if you choose to
have the relay acknowledgeable from the LevelCom 100 front panel ACK key.
8. Press ENTER. SAVING will appear briefly on the display. If SYS FAIL was selected
press ESCAPE to back out of the menu. If ALARM was selected please continue below.
9. The unit will display HI HI.
10. Press the UP or DOWN keys to scroll through the menu selections.
11. Press MENU key to select those alarms you wish activated.
12. Press ENTER. SAVING will appear briefly on the display and the display will shift to
ALARM.
13. Press ESCAPE to return to normal operation.
Control Relay Configuration
When a relay is set up as a control relay there are two setpoints that must be defined; the on
setpoint and the off setpoint. The relay will be energized when the level reaches the ON
SETPOINT value and the relay will be de-energized when the level reaches the OFF
SETPOINT value. This is simple enough but there are other factors to consider before
setting the relays up.