EasyManua.ls Logo

Levelcom 100 - The Hardware Menu

Default Icon
101 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 85
©2013 Technical Marine Service, Inc. LC-100 V2.97
Verify that the Modbus Address is set correctly. See Modbus Communication in the
advanced Setup section of this manual.
Verify that the baud rate and parity settings are correct. There are some complications with
the parity settings, especially in the case where no parity information is sent. In
communications with desktop computers the most common parity setting is N-8-1, no parity,
8 bits per byte, 1 stop bit. In some PLCs though the only available no parity setting is
equivalent to N-8-2, no parity, 8 bits per byte, 2 stop bits. When there is a mix up between
these types the machines will communicate sometimes, but not reliably, or only in one
direction. The second stop bit can sometimes be detected as the start bit of the next byte if
an N-8-2 setup is communicating with a N-8-1 setup. This results in framing errors at the
receiving end and failed communication. See the Serial Communication section on page 30.
Under the COMM SETUP menu in the UTILITIES menu there is an item called DIAGS. The
standard Modbus error counters are accessible here and they can be useful to help
troubleshoot Modbus communication problems. The items in this menu are as follows
EVENT COUNT: Counts messages sent to the LevelCom 100 that were successfully
received and processed.
EXCEPTION COUNT: Counts messages sent to the LevelCom 100 that were successfully
received that generated exceptions. These are messages that cannot be serviced because
of parameters out of bounds, or there is a command that is not supported by the LevelCom
100.
MESSAGE COUNT: Counts all messages on the Modbus network, including messages not
directed at the LevelCom 100.
CRC ERROR COUNT: Counts messages sent to the LevelCom 100 who’s calculated CRC
did not agree with the CRC in the message. This suggests noise in the network is garbling
message traffic. If this counter is counting continuously check the network wiring for faults or
bad connections.
CLEAR COUNTERS: This utility is used to clear the Modbus counters. This is useful when
you start troubleshooting to see what the counters are doing now. If the network has been
operating continuously for a long time there may be non-zero count values on the error
counters even if the events counted are relatively rare. It is important to know if there is a
real problem or not. Clear the counters at the beginning of a troubleshooting session to
avoid confusion. The values of the error counters are also remotely readable through the
Modbus interface. See the Modbus register map section on page 91
The HARDWARE Menu
There is a special menu on the LevelCom 100 that is used to configure or read installed
hardware options. Most of these options are indications only and are not changeable by the

Table of Contents