©2013 Technical Marine Service, Inc. LC-100 V2.97
12. Press DOWN until the machine displays MIN CURRENT.
13. Press ENTER. The unit will display 0.0.
14. Press the UP or DOWN keys to scroll to the Minimum Current you have defined on your
worksheet.
15. Press ENTER. SAVING will appear briefly on the display and the display will shift to MIN
CURRENT.
16. Press DOWN until the machine displays MAX SETPOINT
17. Press ENTER. The unit will display 0.0.
18. Press the UP or DOWN keys to scroll to the MAX SETPOINT value you have defined on
your worksheet.
19. Press ENTER. SAVING will appear briefly on the display and the display will shift to MAX
SETPOINT.
20. Press DOWN until the machine displays MAX CURRENT
21. Press ENTER. The unit will display 0.0.
22. Press the UP or DOWN keys to scroll to the MAX CURRENT value you have defined on
your worksheet.
23. Press ENTER. SAVING will appear briefly on the display and the display will shift to MAX
CURRENT.
24. Press ESCAPE to return to normal operation.
Manual Analog Output
The analog output can be operated in manual mode when it is set up as a control output.
This mode can be used to test the system, and any devices that receive the signal from the
LevelCom 100. This may be used to test the system if the output is to be used as a gauge
output as well. The machine must be temporarily set up as a control output to use this
function though, and you must be sure to switch the configuration back to a gauge output
when you are done testing.
1. Enter Program Mode.
2. At SYSTEM press the UP or DOWN keys to scroll to OUTPUTS.