Page 41
©2013 Technical Marine Service, Inc. LC-100 V2.97
11. Press ENTER to save the selection. SAVING will appear briefly on the display and the
display will shift to PURGE.
12. Press DOWN. Unit will display PURGE DURATION.
13. Press ENTER. Unit will display 5 seconds.
14. Press UP or DOWN to set the purge duration (from 5-180 seconds) you need.
15. Press ENTER to save the selection. SAVING will appear briefly on the display and the
display will shift to PURGE DURATION.
16. Press ESCAPE. Unit will display TIMING.
17. Proceed with the next programming step or press ESCAPE twice to return to normal
operation.
Specific Gravity Setup
If Automatic Specific Gravity Option is not installed use this procedure.
1. At TIMING press DOWN. Unit will display SPEC GRAV.
2. Press ENTER. Unit will display 1.000.
3. Press UP or DOWN to scroll to the specific gravity of the liquid stored in the tank.
4. Press ENTER to save the selection. SAVING will appear briefly on the display and the
display will shift to SPEC GRAV.
5. Proceed with the next programming step or press ESCAPE twice to return to normal
operation.
If Automatic Specific Gravity Option is installed there are more items to set up. Use the
following procedure to set up for automatic specific gravity operation.
Note: If the Automatic Specific Gravity option is installed the SG DISTANCE parameter must
be setup under DISPLAY SETUP (page37). If this parameter is not set up correctly
Automatic Specific Gravity will not function.
You can run the LevelCom 100 in either manual or automatic specific gravity. You should set
up a manual specific gravity value even if you intend to operate the machine in automatic.
On power up the manual value of specific gravity is used initially before the first good specific
gravity value is read. Also if there is a problem detected on the specific gravity sense line the