©2013 Technical Marine Service, Inc. LC-100 V2.97
correctly with the default timing parameter value of 1 on over 300 feet of ¼ inch copper
tubing. Poly tubing has a greater resistance to gas flow than similar sized copper tubing.
If you need to set the parameter very differently from the values shown in the table above
and you are using ¼ inch tubing, there is probably something wrong with the installation.
The sense line may be kinked somewhere causing a near complete blockage. Check the
installation first before adjusting the value of this parameter from the normal value of 1.
Adjusting this parameter is the last resort and should not be done without eliminating all other
sense line problem sources first.