L-IP User Manual 118 LOYTEC
Version 6.1 LOYTEC electronics GmbH
corresponding alarm is shown in the column “Node Alarm”. By selecting one or multiple
nodes in the list and clicking on the “Wink selected node(s)” button the corresponding
nodes can be winked using the CEA-709 wink network management command.
If the checkbox “automatically refresh data” is checked data in the device status view is
refreshed every 15 seconds. The page can be refreshed manually by pressing the “refresh”
button.
9.5.4 Channel Statistics
The channel statistics view is used to view statistic data accumulated by the L-IP Redundant
for the two channels connected to the L-IP Redundant. To access the channel statistics view
click on the “Channel Statistics” icon on the left side of the L-IP Redundant Plug-In window
(see Figure 112).
Note: Most of the diagnostic information is only available if the plug-in runs in online mode and
the device is accessible over the network.
Figure 112: The Channel Statistics View.
The channel statistics view has the following elements:
Device up-time
Shows the time elapsed since the L-IP was (re-)booted.
The following data is shown for each channel the L-IP Redundant is attached to
(CEA-709/CEA-852):
Elapsed time
Shows the time since L-IP Redundant powered up or since the statistics for this port where
reset.