L-IP User Manual 51 LOYTEC
Version 6.1 LOYTEC electronics GmbH
Status
Description
registered
The CEA-852 device has been successfully registered with
the IP-852 channel and is fully functional.
unregistered
The CEA-852 device has never been registered with the
IP-852 channel.
not contacted
The CEA-852 device has not been contacted since the
configuration server has started.
not responding
The CEA-852 device has been registered but is not
responding at the moment.
disabled
The CEA-852 device has been disabled on the channel (or
rejected).
internal error
The configuration server has detected an internal error.
Please contact LOYTEC support in this case.
Table 4: Possible CEA-852 device states.
r - Recontact devices & list channel members
Select this menu item to contact all CEA-852 devices on the IP-852 channel and watch the
state of the individual CEA-852 devices.
This menu item can also be used when a CEA-852 device (e.g. L-IP) is replaced and the
CEA-852 configuration must be propagated to the new device without deleting the device in
the configuration server and adding the device again.
This menu item can also be used to remove all auto members from the configuration server
that are no longer responding.
5.9 Reset configuration (load factory defaults)
This menu item allows resetting the device into its factory default state. The following menu
appears.
Reset Configuration Menu
========================
[1] Reset everything to factory defaults
[2] Reset switch configuration to factory defaults
[3] Reset all passwords
[q] Quit
Please choose:
Figure 41: Reset to factory defaults menu.
1 - Reset everything to factory defaults
This option resets the complete device to factory defaults. This includes IP settings and the
CEA-709 routing functionality according to the DIP-switch settings.
2 - Reset switch configuration to factory defaults
This option resets only the forwarding tables for the L-IP when used in smart switch mode
(see Section 7.1.2). Use this menu item if you are moving CEA-709 network nodes between
different CEA-709 channels.