Address
for
commu
nication
Sets the code number to jump.
Stores information on the types of faults,
the frequency, the current and the
Accel/Decel condition at the time of fault.
The latest fault is automatically stored in
the H 1- [Fault history 1].
Clears the fault history saved in H 1-5.
When run frequency is issued, motor
starts to accelerate after dwell frequency
is applied to the motor during H8- [Dwell
time].
[Dwell frequency] can be set within the
range of F21- [Max frequency] and F23-
[Start frequency].
Sets the time for dwell operation.
Sets the frequency range to skip to
prevent undesirable resonance and
vibration on the structure of the machine.
[Skip
frequency
low limit 1]
Run frequency cannot be set within the
range of H11 thru H16. The frequency
values of the low numbered parameters
cannot be set above those of the high
numbered ones. Settable within the
range of F21 and F23.
[Skip
frequency
high limit
1]
[Skip
frequency
low limit 2]
[Skip
frequency
high limit
2]
[Skip
frequency
low limit 3]
[Skip
frequency
high limit
3]
1)
: only displayed when H10 is set to 1. # H17, H18 are used when F2, F3 are set to 1 (S-curve).