EasyManuals Logo

LSIS sv-ig5a User Manual

LSIS sv-ig5a
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
7-11
Power On Start select
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
drv
[Drive mode]
1, 2
0 ~ 4
1
Function group 2
H20
[Power On Start select]
1
0 ~ 1
0
Set H20 to 1.
When AC input power is applied to the inverter with drv set to 1 or 2 {Run via control
terminal} ON, motor starts acceleration.
This parameter is inactive when drv is set to 0 {Run via keypad} or 3 {RS485
communication}.
CAUTION
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly upon applying AC input power.
Run
command
Frequency
Input voltage
When H20 is 0 When H20 is 1
Restart after fault reset
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Drive group
drv
[Drive mode]
1, 2
0 ~ 4
1
Function group 2
H21
[Restart after fault reset
selection]
1
0 ~ 1
0
Set H21 to 1.
Motor starts acceleration if drv is set to 1 or 2 and the selected terminal is ON when a fault
is cleared.
This parameter is inactive when drv is set to 0 {Run via keypad} or 3 {RS485
communication}.
CAUTION
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly after the fault is cleared.
For Service Call 800-848-2504
For Service Call 800-848-2504

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS sv-ig5a and is the answer not in the manual?

LSIS sv-ig5a Specifications

General IconGeneral
BrandLSIS
Modelsv-ig5a
CategoryInverter
LanguageEnglish

Related product manuals