Chapter 3 Analog Output Module (XBF-DV04A, XBF-DC04A, XBF-DC04B)
3 - 29
3.14.3 Analog output value is not normal.
D/A conversion value is 0.
Channel status is set as Enable.
External power (DC 24V) is supplied.
Check and correct the channel status on the I/O parameter.
Supply external power (DC 24V)
Refer to 2.8.2 and wire properly.
Wiring of each channel is normal.
Input voltage/current of external terminal
block is normal.
Set U0x.02 to enable the output referring to p3-19
No
Yes
No
Yes
No
Yes
No