Chapter 4 RTD Input Module (XBF-RD04A, XBF-RD01A)
 
4.2.2 Performance specifications 
 
Here describes general specifications of RTD input module. 
Item 
Specifications 
XBF-RD04A  XBF-RD01A 
No. of input channel  4 channels  One channel 
Input sensor 
type 
PT100  JIS C1604-1997 
JPT100  JIS C1604-1981 , KS C1603-1991 
Temperature 
input range 
PT100  -200 ~ 600℃ 
JPT100  -200 ~ 600 ℃ 
Digital output 
PT100  -2000 ~ 6000 
JPT100  -2000 ~ 6000 
Scaling display 
0 ~ 4000 
Accuracy 
Normal 
temp.(25 ℃) 
Within ±0.3%   
Full temp.(0~55
  Within ±0.5%   
Conversion speed  40ms / channel 
Insulation 
Non-insulation 
Terminal to PLC 
Power 
  Insulation (Photo-Coupler) 
Terminal block  15-point terminal block 
I/O points occupied  Fixed type: 64 points 
Wiring method  3-wire 
Max. number of equipment 
7 (when using XBM(C)-DxxxS type) 
10 (when using XB(E)C-DxxxH type) 
Function 
Filtering  Digital filter (160 ~ 64000ms) 
Alarm  Disconnection detection 
Current 
consumption 
Inner DC5V  100㎃ 
external DC24V  100㎃ 
Weight  63g 
 
 
 
 
 
 
 
 
 
4 - 3