Chapter 5 Thermocouple Input Module (XBF-TC04S,TC04B) 
 
(d) This area shows the same results with sensor type designation in I/O parameter setting window. 
 
 
(3) Temp. unit setting area (Address 5) 
(a) Temp. unit (Celsius/ Fahrenheit) of thermocouple input module can be set per channel.   
(b) In case of PUT instruction, Temp. unit setting area is as follows. 
 
—  —  —  —  —  —  —  —  —  —  —  — 
C 
H 
3 
C 
H 
2 
C 
H 
1 
C 
H 
0 
 
 
(c) Vales set in B4 ~ B15 are ignored. 
(d) This area shows the same results with temp. unit setting in I/O parameter setting window. 
 
 
 
(4) Filter constant setting area (Address 6~9) 
(a) Filter constant can be set per channel. 
(b) Filter constant ranges 0 or 200 ~ 64000.   
(c) If filter constant is set as 0, filtering process is not executed. 
(d) When input is 1~199 or larger than 6400, 0 (filter disable) is selected by force.   
But, U0x.01.8~ U0x.01.B  (setting error representation, in case of IEC type, %UX0.x.24 
~ %UX0.x.27) are on, error information is displayed at bit 1 of address 27~30. 
(e) In case of PUT instruction, filter constant setting address is as follows. 
5 - 45