XGB Analog edition manual 
 
8.11.2 Operation Parameter Setting Area 
The operation parameter setting area of the analog mix module is as follows. 
 
Description    Setting  R/W  Command 
0  Enable channel  Bit Off (0): disable, Bit ON (1): enable  R/W 
PUT/GET 
1  Input    range setting 
Input range setting (4 bit per channels) 
0: 4 ~ 20   
1: 0 ~ 20   
2: 0 ~ 10 V 
R/W 
2  Output data type setting 
Output data type setting   
(4 bit per channels) 
0: 0 ~ 4000 
1: -2000 ~ 2000 
2: Precise value 
3: 0 ~ 1000 
- In case of precise value 
4 ~ 20  : 400 ~ 2000 
0 ~ 20  : 0 ~ 2000 
0 ~ 10 V: 0 ~ 1000 
R/W 
3 
Input channel 0 count 
average value setting   
0 or 2 ~ 64000 [times] 
R/W 
4 
Input channel 1 count 
averaging value setting   
R/W 
9 
Input channel 0 gain 
weighting 
-40~40 
R/W 
10 
Input channel 1 gain 
weighting 
R/W 
13  Setup error information   
10#: input ch range setting error 
20#: input ch data type setting error 
30#: input ch average value setting error   
40#: input ch gain weighting setting error 
R  GET 
 