Chapter 9 Analog Output Option Board (XBO-DA02A)
 
9.2.2 Performance specifications 
 
Here describes performance specification of analog output module. 
Item  Specification 
Analog 
output 
range 
Range 
DC 0 ~ 10V 
(Load resistance: 2
㏀  Min.) 
DC 4 ~ 20
㎃ 
DC 0 ~ 20
㎃ 
(Load resistance: 450Ω Max.) 
Output range can be set at user program or I/O parameter for each 
Digital 
input 
Type  12-bit binary data 
Range 
Unsigned 
0~4000 
Signed value  -2000 ~ 2000 
Precise value  0 ~ 1000 (DC0~10V) 
400 ~ 2000 (DC4~20
㎃) 
㎃
Percentile value
0 ~ 1000 
Maximum resolution 
1/4000 (DC 4 ~ 20㎃: 1/3200) 
2.5㎷  (DC 0 ~ 10V) 
㎂
㎃
㎂
㎃
Additional function 
Channel output state setting (former, min, middle, max value) 
Insulation method 
no insulation between analog output channels   
no insulation between output terminal and PLC main unit   
㎃
 
Note1) In order to use analog output option board, the following version is needed. 
 
Main unit  Version information 
 
Note2) 
Offset/gain value on analog I/O range can be adjusted at XG5000 - I/O parameter 
9 - 3