XGB Analog edition manual 
 
(2) Output performance specification 
Output performance specification 
Analog 
output 
range 
Range 
DC 0 ~ 10V 
(Load resistance: 2kΩ Min.) 
㎃
DC 0 ~ 20㎃ 
(Load resistance: 450 Ω Max.) 
Set at user program or I/O parameter per each channel per each 
Digital 
input 
Range 
Unsigned 
0 ~ 4000 
0 ~ 1000 (DC 0 ~ 10V) 
400 ~ 2000 (DC 4 ~ 20mA) 
0 ~ 2000 (DC 0 ~ 20mA) 
Percentile 
0 ~ 1000 
Max. resolution 
㎃
2.5㎷  (DC 0~10V) 
㎂
㎃
㎂
㎃
Additional function 
(select among former, min, middle, max value) 
 
 
(3) I/O Common performance specification 
I/O common performance specification 
Insulation method 
Non-insulation betweens analog I/O channels 
Non-insulation between I/O terminal and PLC main unit 
㎃
 
Note1) In order to use analog I/O option board, the following version is needed. 
 
Main unit  Version information 
 
Note2) Offset/gain value on the analog output range can be adjusted at XG5000- I/O parameter 
10 - 4